Metal oxide arrester test selection scheme

Metal oxide arrester selection scheme

cycle Claim Description

1) Power plant and substation lightning arresters before the annual thunderstorm season

2) When necessary

1) Above 35kV, not less than 2500MΩ

2) 35kV and below, no less than 1000MΩ

Use 2500V and above megger

DC 1mA voltage (U1mA) and leakage current at 0.75U1mA

cycle Claim Description

1) Power plant and substation lightning arresters before the annual thunderstorm season

2) When necessary

1) Must not be lower than the value specified in GB11032

2) The measured value of U1mA should be no more than ±5% compared with the initial value or the manufacturer's specified value.

3) The leakage current at 0.75U1mA should not exceed 50μA

1) Record the ambient temperature and relative humidity during the test

2) Shielded wire should be used for the wire for measuring current

3) The initial value refers to the measured value at the time of the handover test or the production test.

AC leakage current at operating voltage

cycle Claim Description

1) Newly put into operation 110kV and above will be measured once after 3 months of operation; once every six months; after one year of operation, once before the thunderstorm season every year.

2) When necessary

Measuring full current and resistive current at operating voltage
Or power loss, the measured value is compared with the initial value. When there is a significant change, the monitoring should be strengthened. When the resistive current is increased by 1 time, the power failure should be checked.

The ambient temperature, relative humidity, and operating voltage at the time of measurement should be recorded. The measurement should be carried out when the surface of the porcelain sleeve is dry, and attention should be paid to the influence of phase interference.

Base insulation resistance

cycle Claim Description

1) Power plant and substation lightning arresters before the annual thunderstorm season

2) When necessary

Self-regulation

Use 2500V and above megger

Check the discharge counter action

cycle Claim

1) Power plant and substation lightning arresters before the annual thunderstorm season

2) When necessary

Test 3-5 times should be normal action, the counter indication should be adjusted to "0" after the test

Constant Voltage LED Driver

The KSPOWER brand constant voltage led driver provides L series with 4 functions optional: 5 in 1 dimmable(0-10V/1-10V/Triac/PWM/resistor), non dimmable, triac/phase-cut dimmable, 4 in 1 dimmable(0-10V/1-10V/resistance and PWM signal) constant voltage LED Drivers; N series phase dimmable LED driver; E series junction box LED driver and P series LED Driver. The constant voltage driver is IP65 IP67 NEMA 3R IP20 rated environment protection for indoor and outdoor LED lighting, with or without junction box for easy installation. The led grow light driver is Class 2 Class P rated and high built-in PFC function, offers 5 years after-sale warranty and both ETL/cETL, UL/cUL, FCC CE ENEC GS RoHS Listed and SELV style enclosures. The led electronic driver transformers offers outstanding led dimming and power performance, flicker free and protections for short circuit, over load, over voltage and over temperature. The P series LED driver compact small plastic unit size for built-in LEDs.